testo 557s Smart Vacuum Kit - Smart digital manifold with wireless vacuum and clamp temperature probes
- Completely wireless measurements and all results at a glance: thanks to Bluetooth probes and large graphic display
- Exceptionally compact and reliable thanks to the easy-to-handle, robust housing with IP 54 protection class
- Easy, wireless, flexible measurements and documentation: Temperature and vacuum measurements via automatic Bluetooth® connection, testo Smart App for documentation and lots more
- In the kit: testo 557s smart digital manifold with Bluetooth and 4-way valve block, 1 x testo 552i wireless vacuum probe (Bluetooth), 2 x testo 115i wireless clamp temperature probes (Bluetooth, NTC), case
Internal Reference :
0564 5571Description
Easier, more flexible measurements and documentation: With the testo 557s digital manifold with Bluetooth and 4-way valve block, you‘ll be ideally equipped for your measuring tasks in the field of commissioning, servicing and maintenance of refrigeration and air conditioning systems and heat pumps.
Delivery Scope
testo 557s digital 4-way manifold including batteries (4 x AA) and calibration protocol
- 1 x testo 552i wireless Bluetooth vacuum probe
- 2 x testo 115i wireless Bluetooth clamp thermometers
- Transport case
- testo Smart App (free download)
- Instruction manuals
Parameters | |
---|---|
Measuring range | -50 to +150 °C |
Accuracy | ±0.5 °C |
Resolution | 0.1 °C |
General technical data | |
Weight | 1243 g |
Operating temperature | -20 to +50 °C |
Protection class | IP54 |
Battery Life | 250 h with no illumination, no Bluetooth<sup>®</sup>; 100 h with illumination and Bluetooth<sup>®</sup> |
Battery type | 4 x type AA batteries |
Refrigerants in instrument | R114; R12; R123; R1233zd; R1234yf; R1234ze; R124; R125; R13; R134a; R22; R23; R290; R32; R401A; R401B; R402A; R402B; R404A; R407A; R407C; R407F; R407H; R408A; R409A; R410A; R414B; R416A; R420A; R421A; R421B; R422B; R422C; R422D; R424A; R427A; R434A; R437A; R438A; R442A; R444B; R448A; R449A; R450A; R452A; R452B; R453a; R454A; R454B; R454C; R455A; R458A; R500; R502; R503; R507; R513A; R600a; R718 (H₂O); R744 (CO₂) |
Refrigerants update via App | R11; FX80; I12A; R1150; R1270; R13B1; R14; R142B; R152A; R161; R170; R227; R236fa; R245fa; R401C; R406A; R407B; R407D; R41; R411A; R412A; R413A; R417A; R417B; R417C; R422A; R426A; R508A; R508B; R600; RIS89; SP22 |
Pressure Measurement | |
Probe connection | 2 x plug-in (NTC) |
Measuring range pressure | -1 to 60 bar |
Accuracy pressure | ±0.5 % fs |
Resolution pressure | 0.01 bar |
Probe connection pressure | 3 x 7/16" – UNF + 1 x 5/8'' – UNF |
Overload rel. (high pressure) | +65 bar |